only search RISE web site

Information Portal

Design Worksheet

System Sizing Worksheet for RE Display System 3 at ROTA

Inverter Sizing

Parameter

Label

Notes

Battery Charge Controller (BCC) efficiency
98%
A1
From Initial design Specification
System Voltage
12 Vdc
A2
From Initial design Specification
 
 
Maximum Power Required
50 W
A3
Selected based on Maximum Demand
Total Energy Used
148 Wh
A4
from Energy Calculation
Current Draw at Maximum Demand
4.2 Amp
A5
3.4.1(a) recommends a limit of no greater than 120 Amp
System Voltage Suitability
Yes
 
 
 
BCC Inefficiency with load
151 Wh
A6
=A4/A1
Total A-h per day
12.6 Ah
A7
=A6/A2
Over supply coefficient fo RE only systems
1
A8
3.4.2.5 Systems without a generating set
Selected BCC Specifications
Morningstar SunLight SL10
A9
 
BCC Efficiency
98%
 
 
 
Battery sizing
 
Number of days of autonomy
3 Days
B1
From Initial design Specification
Max depth of discharge
60%
B2
From Initial design Specification
Battery Capacity
63 Ah
B3
=A7*A8*B1/B2
Lowest 24 hr Temperature
25°C
B4
Typical ambient condition
Temperature Correction Factor
1
B5
From battery specifications
Adjusted Battery Capacity
63 Ah
B6
=B3/B5
Selected battery
GNB Vented leadacid Cell" 12V OGi 50 LA"
B7
Selected
Selected Battery Voltage
12 V
From battery specifications
Selected battery discharge rate
C10
B8
From battery specifications
A-hr capacity of selected battery
50 Ah
B9
From battery specifications
Number of batteries in parrallel
1
B10
=B6/B9 (Rounded up)
Number of batteries in series
1
B11
=A3/12
Check: Capacity of selected battery at 10h rate
50 Ah
B12
From battery specifications
Capacity of battery bank at 100hr rate
50 Ah
B13
=B12*B10
Max. Daily depth of discharge
25%
B14
=A7/B13
Suitability of batteries?
YES
B15
 
Estimated cycle life @ Max. Daily depth of discharge
approx. 3500 cycles
From battery specifications
Total number of batteries
1
=B10*B11
 
 
Photovoltaic Array sizing
 
Design tilt
~ 35°
C1
From Initial design Specification
Design Month
Yearly Average
C2
From Initial design Specification
Daytime Average Ambient Temperature for Period
20°
T1
Selected from site data applicable when using MPPT controllers AS4509.2 clause 3.4.3.6
Average Daily cell operating temperature
45°
T2
T2=T1 + 25 AS4509.2 clause 3.4.3.6
Total Energy demand per day
12.6 Ah
C3
=A7*A8
Battery efficiency
85%
C4
From battery specifications
Array Output required per day
14.8 Ah
C5
=(C3/C4)
Peak sun hours at design tilt for design month
5.6 hrs
C6
From Initial design Specification (AUST Solar Rad data)
Selected module
BP Solar, BP275 Modules
 
Maximum Power
75W
C7
 
Selected module I at 14V at NOCT
4.55 Amp
C8
From panel specification sheet
Selected module Power at 14V at NOCT
64 W
=C18*14
Selected module nominal operating voltage
12 Vdc
C9
From panel specification sheet
Derating Factor for manufacturing tolerences
95%
f m
From module specification sheet (note BP Solar minimum power tolerance is with minus 5 W from nominal power ) AS4509.2 clause 3.4.3.5
Derating Factor for soiling tolerances
95%
f s
 
Derated Current
4.1 Amp
C10
=f m * f s *C8 (note spec for module is no more than -5W from nominal rating) AS4509.2 clause 3.4.3.7(1)
Derated Power of Module
57.4 W
.
AS4509.2 clause 3.4.3.7(2)
Number of modules in series
1
C11
=A2/C9
Output per module
23.0 Ah
C12
=C10*C6
Number of strings of modules in parallel
1
C13
=C5/C12
Number of Panels
2
C14
Decided for high reliability
Total derated Output
115 W
C15
=C14*C10*14
Total Rated Peak Output
150 W
C16
=C7*C14
 
 
Note: Average Solar radiation data

 

Return to Casestudy

 

 

 
Home Print Friendly Sitemap Contact Us